NCMA TEK 10-02D Crack Control Standard

CMU Control Joint Calculator

Under NCMA TEK 10-02D, a 50×8 ft reinforced CMU wall requires 2 vertical control joints spaced at maximum 20 ft (L/H ≤ 2.5). The assembly requires 48 sash blocks, 16 LF of rubber shear key, and 1 20-oz caulk sausages.

Size maximum allowable crack-control joint spacing, slotted sash CMU units, extruded rubber shear keys, closed-cell backer rods, and polyurethane caulk under NCMA TEK 10-02D and TMS 402 specifications.

Live Joint Spacing Takeoff
2Joints(Max 20' Spacing · 48 Sash Blocks)
Details

Total unbroken horizontal wall run between corners.

Vertical height from top of footing to top of bond beam.

ASTM A951 wire allows up to 25 ft joint spacing under NCMA TEK 10-02D.

Transfers lateral out-of-plane wind loads while allowing longitudinal shrinkage.

Control Joint Takeoff

Vertical Control Joints Required

2Joints

Max Spacing: 20 ft on-center (NCMA TEK 10-02D)

Sash CMU Blocks48Slotted stretcher units
Rubber Shear Key16'Full vertical run length
20-oz Sealant1Sausages (~2 10-oz tubes)
Wall Panels3Avg 16.7 ft panel length
Closed-Cell Backer Rod:16 Linear Feet
Estimated Materials Cost:~$207
Blocks: $156
Key: $30
Backer: $6
Caulk: $15

NCMA TEK 10-02D Rule

Continuous horizontal wire reinforcement must stop at the control joint. Never bridge mortar joints or run horizontal bed wire continuously through a vertical control joint.

NCMA Control Joint Spacing & Material Reference Table

Standard control joint spacing rules per NCMA TEK 10-02D Table 1 for walls with horizontal bed joint reinforcement (W1.7 wire @ 16" o.c.) versus unreinforced plain masonry. Material takeoffs assume 8" high courses and 3/8" wide joints.

Wall HeightWire Reinforced Max SpacingPlain Masonry Max SpacingSash Blocks / JointShear Key / JointSealant (20-oz)
6 ft (9 courses)15.0 ft (2.5 H)12.0 ft (2.0 H)9 blocks6 LF1 tube
8 ft (12 courses)20.0 ft (2.5 H)16.0 ft (2.0 H)12 blocks8 LF1 tube
10 ft (15 courses)25.0 ft (Max Limit)20.0 ft (Max Limit)15 blocks10 LF1 tube
12 ft (18 courses)25.0 ft (Max Limit)20.0 ft (Max Limit)18 blocks12 LF1 tube
16 ft (24 courses)25.0 ft (Max Limit)20.0 ft (Max Limit)24 blocks16 LF2 tubes
20 ft (30 courses)25.0 ft (Max Limit)20.0 ft (Max Limit)30 blocks20 LF2 tubes

* Note: Under NCMA TEK 10-02D, continuous bed joint reinforcement allows length-to-height ratios up to L/H ≤ 2.5 with a hard cap of 25 feet. Without reinforcement, maximum spacing is capped at min(20 ft, 2.0 H).

Why Concrete Masonry Walls Require Control Joints

Unlike clay brick masonry, which expands permanently over time through moisture absorption, concrete masonry units (CMU) undergo continuous drying shrinkage after manufacture and installation. As water hydrates Portland cement in the block matrix and moisture evaporates to ambient air, tensile stresses build within the masonry assembly.

Because concrete masonry has high compressive strength but limited tensile capacity (typically 10% of compressive strength), unmitigated shrinkage stress manifests as random, unsightly stair-step cracking through mortar joints and block webs. Control joints pre-determine and localize these stress relief points into clean, sealed vertical planes.

Key Components of an Engineered CMU Control Joint

A code-compliant control joint is a complete structural assembly consisting of four coordinated components:

  • Sash CMU Blocks: Stretcher blocks molded with a vertical end keyway slot. They provide aligned vertical recesses on both faces of the joint plane to house the shear key.
  • Rubber / Neoprene Shear Key: An extruded cross-shaped or dumbbell gasket (ASTM D2000) that sits between sash blocks. It transfers out-of-plane lateral loads (such as hurricane wind or seismic pressure) across adjacent wall panels while permitting unrestricted longitudinal shrinkage.
  • Closed-Cell Foam Backer Rod: A resilient polyethylene cylinder (ASTM C1330 Type C) inserted into the outer 1/2-inch of the joint. It controls caulk depth and prevents three-sided adhesion, which would tear the sealant when panels pull apart.
  • Elastomeric Joint Sealant: High-movement polyurethane or neutral-cure silicone (ASTM C920 Class 25 or 50) that remains flexible through sub-zero freeze cycles and summer heat expansion.

Step-by-Step Installation: How to Build a CMU Control Joint

  1. Establish Layout & Spacing: Mark control joint locations on the foundation footing before laying the starter course. Ensure spacing does not exceed 25 feet or 2.5 times wall height, and verify joints align with door/window jambs and wall height offsets.
  2. Lay Sash Blocks with Interrupted Mortar: Lay sash CMU blocks at the joint line. Apply mortar to block face shells as usual, but keep the vertical end head joint completely free of mortar where the shear key will be inserted.
  3. Insert Preformed Rubber Shear Key: Slip the continuous rubber or PVC shear key into the vertical end grooves as courses rise. Ensure the key remains plumb and spans fully across the course transition.
  4. Stop Horizontal Bed Wire Reinforcement: Cut horizontal ladder or truss wire cleanly at each side of the control joint. Never allow wire to span across the joint line.
  5. Detail Bond Beam Slip Dowels: Where continuous horizontal bond beams are structurally required, insert smooth steel rebar dowels with one side greased or placed inside a closed-end plastic dowel sleeve.
  6. Rake Joint & Install Backer Rod: Rake the outer face joint back 3/4 inch deep. Press a closed-cell foam backer rod into the joint, compressing it by 25% to leave a uniform 3/8-inch recess for caulk.
  7. Tool Elastomeric Sealant Bead: Gun high-performance ASTM C920 polyurethane sealant over the backer rod. Tool the bead with a concave jointing tool to create an hourglass cross-section that maximizes elongation capability.

Control Joints vs. Expansion Joints: The Critical Difference

In commercial architecture, control joints and expansion joints serve fundamentally opposite kinematic roles:

CMU Control Joint (Shrinkage)

Designed for contraction. Blocks shrink as water leaves the concrete matrix. The joint opens wider over time. Features a shear key for out-of-plane wind support.

Clay Brick Expansion Joint (Expansion)

Designed for expansion. Fired clay bricks permanently expand as they absorb ambient humidity. The joint narrows over time and requires compressible filler.

Structural & Wind-Load Advisory

Control joint placement creates independent structural wall panels. In high-wind zones (ASCE 7) or seismic design categories C through F, out-of-plane shear keys, bond beam slip dowels, and pilaster spacing must be verified by a licensed structural engineer. Never eliminate control joints to simplify bond beam construction.

Calculation Assumptions & References Planning Reference

Material estimates depend on the selected dimensions, product yields, and waste allowance.

Content date: October 2026
Related references: NCMA TEK 10-02D (Control Joints for Concrete Masonry Walls), TMS 402/602 (Building Code Requirements and Specification for Masonry Structures), ASTM C920 (Standard Specification for Elastomeric Joint Sealants), ASTM D2000 / ASTM D2287 (Rubber and PVC Gaskets & Shear Keys). Confirm the applicable edition and local requirements.
A material estimate is not a structural design or code approval.
Masonry Q&A

CMU Control Joint FAQ

Technical answers on joint spacing rules, sash blocks, rubber shear keys, caulk yield, and bond beam slip dowels.

Under NCMA TEK 10-02D and TMS 402, control joints in walls with continuous horizontal bed joint reinforcement (W1.7 wire at 16 inches on-center) must not exceed 25 feet or 2.5 times the wall height (L/H ≤ 2.5). In plain unreinforced walls, maximum spacing decreases to 20 feet or 2.0 times wall height (L/H ≤ 2.0). For an 8-foot-high reinforced wall, maximum allowable spacing is 20 feet.